Why Doors Slam and Heaters Struggle in Winter
These look like five separate problems. They’re usually one problem.Every winter, the same calls come in from plants and warehouses:
- The man door at the shipping office is so hard to push open that people put their shoulder into it, and when it does open, it slams shut behind them.
- Cold drafts roll across the docks even with the overhead doors closed.
- A gas heater keeps going out, or the maintenance crew smells flue gas near the water heater.
- Exhaust fans are running but don’t seem to pull anything.
- The welding smoke, dust, or fumes that used to clear out now hang in the air all shift.
The Building Is Starved for Air
Every exhaust fan in a building pushes air out: welding exhaust, paint booth fans, dust collectors, process hoods, restroom fans, even combustion equipment. Air that leaves has to be replaced. When nothing is designed to bring it back in, the building goes into negative pressure and starts pulling air from wherever it can, through door cracks, dock seals, wall penetrations, and even backward down heater flues.
That’s why the door fights you and then slams. It’s why cold air pours in at the docks, and why a heater’s exhaust can be pulled back into the space. It’s also why exhaust fans “quit working”: a fan can’t move air out of a building that has no air coming in.
The fix for all five symptoms is the same, and it’s make-up air.
Why Winter Makes It Worse
In summer, the building gets help. Doors are propped open, windows are cracked, and dock doors stay up most of the day, so exhaust air is replaced without anyone thinking about it.
In winter, everything gets closed up to hold the heat in, but the exhaust fans keep running. Now the only path for replacement air is through cracks and gaps, and the air coming through them is cold. Opening a door or window to relieve the pressure just dumps freezing air onto the floor. The building needs air brought in on purpose, and it needs to be heated on the way in.
The Fix: Match Make-Up Air to Exhaust
Start by adding up the exhaust, every fan and hood that moves air out of the building, in CFM. Then size the make-up air unit to replace that volume, with tempered air delivered where people work, not just wherever it leaks in. Most facilities aim to supply about as much as they exhaust, or slightly more, so the building sits neutral or a little positive instead of negative.
When supply matches exhaust, doors open and close normally, drafts at the docks go away, heaters vent the way they’re supposed to, and exhaust fans pull what they were designed to pull. For the details of getting the numbers right, see Five Common Mistakes Engineers Make Sizing Make-Up Air.
Direct-Fired vs. Indirect-Fired Make-Up Air
There are two main ways to heat make-up air with gas.
Direct Gas-Fired
92 to 95 percent thermal efficiencyDirect gas-fired units put the burner flame right in the airstream, so nearly all of the heat goes into the supply air. That makes them more efficient, typically around 92 to 95 percent thermal efficiency. They’re a strong fit for warehouses, distribution centers, and manufacturing floors that need large volumes of tempered air at a low operating cost. Standard direct-fired units are listed for 100 percent outside air and don’t recirculate room air across the burner. Separately listed recirculating designs, often called 80/20, mix some room air back in, with outdoor-air minimums and listing safeguards built in. Keep in mind that the efficiency advantage only matters where combustion products are acceptable in the supply air.
Indirect Gas-Fired
80 to 85 percent thermal efficiencyIndirect gas-fired units burn the gas inside a heat exchanger and vent the combustion products out a flue, so the supply air never touches the flame. Some heat is lost up the flue, so they typically run around 80 to 85 percent thermal efficiency. In exchange, you get clean, combustion-free supply air for food processing, sensitive processes, occupied spaces, and anywhere combustion products aren’t acceptable.
The right choice comes down to the application. Direct-fired gives the most heat for the gas dollar, and indirect-fired gives clean air with no combustion products. For a deeper comparison, read Direct vs. Indirect-Fired Make-Up Air.
On the Job: Warehouse Distribution and Assembly
A warehouse distribution center with an assembly area needed to heat a large space efficiently through cold weather, while also bringing in fresh air to help keep the space clean. Bessamaire supplied a vertical JHV 80/20 direct gas-fired unit moving 40,000 CFM at 92 percent efficiency. It recirculates 80 percent of the room air with 20 percent outside air, and it can switch to 100 percent outside air when the building needs it. The result was energy savings, temperatures held across the space, and reliable uptime through the season.
More jobs like this one are on our Case Studies page.
If your doors are slamming and your heaters are struggling this winter, don’t start with the heater. Start by adding up your exhaust.
Bessamaire, Made in America. Call (800) 321-5992 or send us your exhaust numbers and we’ll help size the make-up air.
Contact Bessamaire today for expert assistance. We calculate air changes, optimize unit placement, and enhance employee well-being. Get budget estimates and comprehensive submittals from us.
Ready to Get Started?
Get In Touch With Our HVAC Experts
Give us a call or fill out the form below and we’ll be in touch as soon as possible. *marks required fields
